Technical Summary
Application
|
LV and MV (208V - 38 kV)
|
Configuration
|
Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
|
Modes of Operation
|
Emergency standby, island, utility paralleling
|
Generator Protective Devices
ANSI Protective Devices
|
15/25, 27/59, 81 O/U, 32, 40, 50, 51
|
Utility Protective Devices
ANSI Protective Devices
|
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
|
Environmental Parameters
Certifications
|
IBC, CBC, UBC & OSHPD Certified
|
Control Panel Enclosure
|
NEMA 1 wall-mounted construction
|
Low Voltage Standards
|
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
|
Medium Voltage Standards
|
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
|
Operating Temperature
|
0°C to 50°C
|
Storage Temperature
|
-20°C to +60°C
|