fbpx
Skip to content
ATC Service Entrance Rated MCCB & Power Breaker Based ATS

ATC Service Entrance Rated MCCB & Power Breaker Based ATS

More Comfort – More Performance – More Versatility

  • ATC-300+ or ATC-900 on MCCB & Power Breaker ATS products Keyed service entrance switch

    Draw-out type breakers (available on Power Breaker ratings)

    UL 891 for 4000-5000A

  • All controls relays and industrial grade relays

    Lugs are 90� rated and all control wire is #16 AWG, type XLPE with a 125� temperature rating

  • Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges.

    The hinges have removable hinge pins to facilitate door removal and are supplied with pad-lockable latches.

Technical Summary

Rating Range 30-5000A
Switch Type Molded Case and Power Breaker
Transfer Type Open / Closed / Delayed

Ratings

Applicable Testing
UL 1008 listed up to 3200A

4000A, and 5000A UL 891 listed
Drawout Power Breaker 200-5000A 2, 3, or 4-Pole
Fixed Mount Power Breaker 200-3200A 2, 3, 4-Pole
MCCB 30-1000A 2, 3, or 4 Pole
System Voltage Application 120-600 Vac 50/60 Hz
Withstand (Power Breaker) Up to 100 kAIC at 600V 3 cycles

Download resources

ATC Service Entrance Rated MCCB & Power Breaker Based ATS Spec Sheet
Cat Gensets Rating Guide

Get info about our financing options

Get The best solution for your job site needs

Let us help.

Name(Required)
Untitled

Call us today: 1-877-778-2230
or  Send us a message